LD is not supported, however, SLD is supported. More Details >>
- No:21054
- Release Date:2018/08/22 16:25
-
Combination of the FR-A800 and MM-BF
Select the models so that "MM - BF rated current value × 1.05 < FR-A820 rated output current value". More Details >>
- No:21000
- Release Date:2018/08/22 16:25
-
UVT will occur when reactor is not connected. Always connect a reactor that matches the motor capacity. More Details >>
- No:20978
- Release Date:2018/08/22 16:25
-
This error occurs when the parameter file is broken. More Details >>
- No:20937
- Release Date:2018/08/22 16:25
-
The calculation is performed by two modes. One method calculates the current winding diameter automatically by moving the dancer roll from lower limit positi... More Details >>
- No:20924
- Release Date:2018/08/22 16:25
-
Monitoring function of the FR-A800-R2R
Line speed command and Line speed pulse monitor can be monitored while the operation is stopping. Actual line speed monitor becomes "0" while the operation i... More Details >>
- No:20914
- Release Date:2018/08/22 16:25
-
Carrier frequency automatic reducing function
The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>
- No:20903
- Release Date:2018/08/22 16:25
-
If Pr.361 = 0, the second terminal can be used as the line speed command when X114 is ON, and as the frequency setting value when X114 is OFF. If Pr.361 = 3,... More Details >>
- No:20891
- Release Date:2018/08/22 16:24
-
Power supply harmonics countermeasure
Use a high power factor converter FR-HC2 or reactor as needed. More Details >>
- No:21115
- Release Date:2018/08/22 16:26
-
Yes, the current response is also improved at the same rate. More Details >>
- No:21079
- Release Date:2018/08/22 16:25