FAQ within [ FREQROL-A800 ]
-
The output of the FM terminal becomes the current output of the CA. More Details >>
- No:21060
- Release Date:2018/08/22 16:25
-
The day of the week is automatically determined from the data of year, month, and day. More Details >>
- No:20997
- Release Date:2018/08/22 16:25
-
UVT will occur when reactor is not connected. Always connect a reactor that matches the motor capacity. More Details >>
- No:20978
- Release Date:2018/08/22 16:25
-
Fuses are not required as peripheral devices for the FR-A802, which has internal fuses. More Details >>
- No:21019
- Release Date:2018/08/22 16:25
-
No alarm occurs due to the abnormal temperature. In the main circuit, alarms such as heatsink overheat will be occurred. More Details >>
- No:20977
- Release Date:2018/08/22 16:25
-
Monitoring function of the FR-A800-R2R
Line speed command and Line speed pulse monitor can be monitored while the operation is stopping. Actual line speed monitor becomes "0" while the operation i... More Details >>
- No:20914
- Release Date:2018/08/22 16:25
-
It is available if the CC-Link option of the FR-A8NC is installed. More Details >>
- No:20894
- Release Date:2018/08/22 16:24
-
Monitoring function of the FR-A800-R2R
No, they cannot be monitored when Pr.363 is other than "5". They are enabled only when Pr.363 = 5. More Details >>
- No:20915
- Release Date:2018/08/22 16:25
-
A tension sensor such as a dancer roll is required for speed control. Because an actual line speed input is required for the winding diameter calculation by ... More Details >>
- No:20926
- Release Date:2018/08/22 16:25
-
If the command is 0.01 Hz or higher, the positioning control is performed. More Details >>