  • Gain adjustment under the speed control

    Since the lower limit has been internally set, 3% or less is recognized as 3%. More Details >>

    • No:21016
    • Release Date:2018/08/22 16:25
  • CC-Link option

    Yes, they are the same. More Details >>

    • No:21010
    • Release Date:2018/08/22 16:25
  • Frequency search of the FR-A800/FR-F800

    DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>

    • No:20831
    • Release Date:2018/08/22 16:24
  • FR-A800

    Number of terminals: There are the same output terminals as A700 and the following terminals (2 points) are added. Safety: SO, SOC * The terminals SO and SOC... More Details >>

    • No:21098
    • Release Date:2018/08/22 16:25
  • Output signal

    The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>

    • No:20995
    • Release Date:2018/08/22 16:25
  • Country of origin

    The country in which the product is manufactured is described on the rating plate as MADE IN JAPAN or MADE IN CHINA. More Details >>

    • No:20956
    • Release Date:2018/08/22 16:25
  • FR Configurator2

    Vector control cannot be selected unless Pr.862 is set to 1. Only the first motor is supported in the motor setting of FR Configurator2. More Details >>

    • No:20840
    • Release Date:2018/08/22 16:24
  • Storage area

    The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>

    • No:20958
    • Release Date:2018/08/22 16:25
  • MT-BU5

    No, the MT-BU5 is not available Use the FR-BU2 instead. More Details >>

    • No:21076
    • Release Date:2018/08/22 16:25
  • Installation necessity of a DC reactor

    A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>

    • No:21077