FAQ within [ FREQROL-A800 ]

11-20 of Total 142

prev 2 / 15page next
  • Installation necessity of a DC reactor

    A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>

    • No:21077
    • Release Date:2018/08/22 16:25
  • The lifetime of EEPROM write

    It is said that the EEPROM has a lifetime of 100,000 write cycles. When the data is written every time the frequency changes, the life of the EEPROM may not ... More Details >>

    • No:20996
    • Release Date:2018/08/22 16:25
  • Sine wave filter

    The sine wave filter can be applied only under V/F control. When Pr.72 PWM frequency selection is set to 25, V/F control is set automatically. The applicable... More Details >>

    • No:21068
    • Release Date:2018/08/22 16:25
  • FR-PU07

    No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>

    • No:21081
    • Release Date:2018/08/22 16:25
  • SW1DND-FRC2 (FR Configurator2)

    Check the setting value of Pr.414 (PLC function operation selection) and if the initial value: 0 (PLC function disabled) is set, set "1" or "2" and enable th... More Details >>

    • No:21080
    • Release Date:2018/08/22 16:25
  • 24 VDC power supply

    Do not remove the jumper of the R1 and S1 when inputting the control circuit power supply from the external 24 V power supply (connecting across the terminal... More Details >>

    • No:21074
    • Release Date:2018/08/22 16:25
  • Output signal

    The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>

    • No:20995
    • Release Date:2018/08/22 16:25
  • Use of the DC reactor

    It can be used in terms of the specifications. However, it is recommended to update the reactor and inverter at the same time because the DC reactor was manu... More Details >>

    • No:21017
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>

    • No:20882
    • Release Date:2018/08/22 16:24
  • FR-A800/FR-F800

    When only the main circuit input power supply is cut off with the MC (when the power supply shutoff time is long), the main circuit undervoltage or instantan... More Details >>

    • No:20833
    • Release Date:2018/08/22 16:24