FAQ within [ FREQROL-A800 ]

11-20 of Total 142

prev 2 / 15page next
  • FR-A800

    - The installation size is compatible for the following capacities. Compatible: 200 V class 90K or lower, 400 V class 7.5K or lower and 18.5K to 280K- The in... More Details >>

    • No:21110
    • Release Date:2018/08/22 16:25
  • FR-DU08

    It cannot be connected. When using DU08, connect it to the PU connector. More Details >>

    • No:21111
    • Release Date:2018/08/22 16:25
  • PLC function

    The number of timer points is 16 for the high speed and low speed in total. More Details >>

    • No:21056
    • Release Date:2018/08/22 16:25
  • Frequency search of the FR-A800/FR-F800

    DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>

    • No:20831
    • Release Date:2018/08/22 16:24
  • 24 VDC power supply

    Power is supplied only to the control power supply, and thus this enables communication, parameter setting through the operation panel or an USB memory devic... More Details >>

    • No:21097
    • Release Date:2018/08/22 16:25
  • Undervoltage warning

    The undervoltage warning of the inverter is judged based on the voltage of the main circuit as follows. Power failure only at the main circuit: Output an und... More Details >>

    • No:20853
    • Release Date:2018/08/22 16:24
  • USB version

    Ver1.1 (Ver2.0 (full speed) compatible). USB1.1 supports Full Speed (12 Mbps) and Low Speed (1.5 Mbps) transmission speed modes. USB2.0 supports High Speed (... More Details >>

    • No:21096
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>

    • No:20881
    • Release Date:2018/08/22 16:24
  • Emergency stop of the FR-A800

    For the V/F control and Advanced magnetic flux vector control, the FR-A800 stops only by Pr.1103 Deceleration time at emergency stop. Pr.815 is not affected. More Details >>

    • No:20860
    • Release Date:2018/08/22 16:24
  • FR-A800 and FR-ALF

    Yes, it can. More Details >>

    • No:20806
    • Release Date:2018/08/22 16:24