Do not remove the jumper of the R1 and S1 when inputting the control circuit power supply from the external 24 V power supply (connecting across the terminal... More Details >>
- No:21074
- Release Date:2018/08/22 16:25
-
When Pr.414 is set to "1" and Pr.388 is set to "0", the PLC function is not enabled unless both the SQ signal from communication and the SQ signal from the e... More Details >>
- No:21073
- Release Date:2018/08/22 16:25
-
The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>
- No:21048
- Release Date:2018/08/22 16:25
-
Only the FR-A800/F800-E series is supported by CC-Link IE Field Basic. (As of March 2017) The FR-A800-GF and FR-A8NCE supported by CC-Link IE Field are not s... More Details >>
- No:20858
- Release Date:2018/08/22 16:24
-
Approximately 2 years when the FR-LU08 is not energized and the real-time clock function is enabled. More Details >>
- No:21084
- Release Date:2018/08/22 16:25
-
For the FR-A700/F700, the hook is cut off for the wiring due to restrictions on the structure. These restrictions are eliminated for the FR-A800/F800. More Details >>
- No:21051
- Release Date:2018/08/22 16:25
-
When the value is written to Pr.646 (Stored winding diameter), the stored value is used. When the value is not written, the minimum or maximum winding diamet... More Details >>
- No:20887
- Release Date:2018/08/22 16:24
-
It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>
- No:20881
- Release Date:2018/08/22 16:24
-
No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
- No:20878
- Release Date:2018/08/22 16:24
-
For the V/F control and Advanced magnetic flux vector control, the FR-A800 stops only by Pr.1103 Deceleration time at emergency stop. Pr.815 is not affected. More Details >>
- No:20860
- Release Date:2018/08/22 16:24