FAQ within [ FREQROL-A800 ]

51-60 of Total 142

prev 6 / 15page next
  • Communication specifications for connection of multiple inverters

    Use the RS485 terminal for the multiple communication of the A series/F series inverters.* Communication with the PU connector is only one-to-one connection. More Details >>

    • No:20998
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    Yes, it can like the standard product. More Details >>

    • No:20880
    • Release Date:2018/08/22 16:24
  • FR-A800-R2R

    If Pr.361 = 0, the second terminal can be used as the line speed command when X114 is ON, and as the frequency setting value when X114 is OFF. If Pr.361 = 3,... More Details >>

    • No:20891
    • Release Date:2018/08/22 16:24
  • Anti-sway control

    Set 3 kg (intermediate value) for the load weight 1 to 5 kg. More Details >>

    • No:20953
    • Release Date:2018/08/22 16:25
  • FR-A800

    When the online auto tuning (magnetic field observer) is enabled, the monitoring accuracy is ± 10%. More Details >>

    • No:20981
    • Release Date:2018/08/22 16:25
  • Front cover

    Parts arrangement is available. Consult with your sales agent. More Details >>

    • No:21012
    • Release Date:2018/08/22 16:25
  • Control power supply

    Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation. Therefore, the separate power supply canno... More Details >>

    • No:21018
    • Release Date:2018/08/22 16:25
  • Frequency setting increment

    The value is displayed in 0.1 rpm increments under Vector control. However, the value is rounded down to the first decimal place and displayed in 1 rpm incre... More Details >>

    • No:21021
    • Release Date:2018/08/22 16:25
  • Safety stop function

    Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>

    • No:21053
    • Release Date:2018/08/22 16:25
  • PLC function

    SD1148 can turn ON multiple bits such as STF and RH simultaneously. SM turns ON bits individually. When SD1148 is H5, it is same as when SM1200 (STF) and SM1... More Details >>

    • No:21057
    • Release Date:2018/08/22 16:25