FAQ within [ FREQROL-A800 ]

61-70 of Total 142

prev 7 / 15page next
  • FR-A800

    No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>

    • No:20878
    • Release Date:2018/08/22 16:24
  • PLC function

    The maximum values are kept. The values are not cleared to zero. More Details >>

    • No:21015
    • Release Date:2018/08/22 16:25
  • FR-A800

    No. Check the parameter setting of the A700, and then adjust the parameter setting of the A800 to those of the A700. For the details, refer to the replacemen... More Details >>

    • No:21107
    • Release Date:2018/08/22 16:25
  • Safety stop function

    Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>

    • No:21053
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>

    • No:20881
    • Release Date:2018/08/22 16:24
  • FR-A800

    No. Check the parameter setting of the A500(L), and then adjust the parameter setting of the A800 to those of the A500(L). For the details, refer to the repl... More Details >>

    • No:21108
    • Release Date:2018/08/22 16:25
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25
  • Terminal response time

    It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>

    • No:20899
    • Release Date:2018/08/22 16:24
  • FR-A800

    By performing offline auto tuning, other manufacturers' IPM, SPM motors can be used under PM sensorless vector control. * When an other manufacturers' magnet... More Details >>

    • No:21106
    • Release Date:2018/08/22 16:25
  • PLC function

    The number of timer points is 16 for the high speed and low speed in total. More Details >>

    • No:21056
    • Release Date:2018/08/22 16:25