FAQ within [ FREQROL-A800 ]

71-80 of Total 142

prev 8 / 15page next
  • Noise filter compliant with the ship classification standards

    It is recommended to use the noise filter manufactured by Soshin Electric Co., Ltd. There is no difference in the filter type depending on the certification ... More Details >>

    • No:21049
    • Release Date:2018/08/22 16:25
  • FR-A800

    Number of terminals: Same input terminals as the A700 series, and the following two terminals are added. Safety: SI1, SI2, SIC 24 V power supply: +24 * The t... More Details >>

    • No:21099
    • Release Date:2018/08/22 16:25
  • FR-PU07

    No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>

    • No:21081
    • Release Date:2018/08/22 16:25
  • FR-A842

    The inrush current limit circuit is not built in the FR-A842 (inverter unit). It is built in the FR-CC2 (converter unit), which is combined with the FR-A842.... More Details >>

    • No:21059
    • Release Date:2018/08/22 16:25
  • FR-A8AZ

    Not available. When using the motor thermistor function, use the dedicated motor V5RU with a thermistor. More Details >>

    • No:21003
    • Release Date:2018/08/22 16:25
  • FR-A8AP

    The ON level is the power supply voltage -3 V or higher and the OFF level is 3 V or lower. More Details >>

    • No:21002
    • Release Date:2018/08/22 16:25
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25
  • Emergency stop of the FR-A800

    For the V/F control and Advanced magnetic flux vector control, the FR-A800 stops only by Pr.1103 Deceleration time at emergency stop. Pr.815 is not affected. More Details >>

    • No:20860
    • Release Date:2018/08/22 16:24
  • Safety stop function

    Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>

    • No:21053
    • Release Date:2018/08/22 16:25
  • Terminal response time

    It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>

    • No:20899
    • Release Date:2018/08/22 16:24