In the FR-A800/F800, the restriction on the wiring length of the shielded cable is eliminated. The wiring length is up to 500 m as is the case with the unshi... More Details >>
- No:21089
- Release Date:2018/08/22 16:25
-
Parameter copy to the USB memory
Yes. Writing is available when the power supply specification or capacity is different. Note that setting values of the voltage relation is also overwritten ... More Details >>
- No:21013
- Release Date:2018/08/22 16:25
-
If Pr.361 = 0, the second terminal can be used as the line speed command when X114 is ON, and as the frequency setting value when X114 is OFF. If Pr.361 = 3,... More Details >>
- No:20891
- Release Date:2018/08/22 16:24
-
- The 280K or lower has the installation size compatibility. - The 315K or higher does not have the installation compatibility; because the inverter unit and... More Details >>
- No:21109
- Release Date:2018/08/22 16:25
-
LD is not supported, however, SLD is supported. More Details >>
- No:21054
- Release Date:2018/08/22 16:25
-
Both settings of Pr.83 and Pr.84 are enabled immediately. However, the output voltage is not changed because the value of Pr.83 has little influence on Vecto... More Details >>
- No:21022
- Release Date:2018/08/22 16:25
-
Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation. Therefore, the separate power supply canno... More Details >>
- No:21018
- Release Date:2018/08/22 16:25
-
The deceleration stop is also performed according to the setting in Pr.815 under V/F control. More Details >>
- No:20957
- Release Date:2018/08/22 16:25
-
The gain of the tension PI gain automatic tuning is the one of the dancer feedback speed control. The gain adjusted by speed control P gain compensation is t... More Details >>
- No:20925
- Release Date:2018/08/22 16:25
-
No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
- No:20878
- Release Date:2018/08/22 16:24