Switching time of the FR-A800 control
20 ms or less is required to switch the control with the MC signal. More Details >>
- No:20838
- Release Date:2018/08/22 16:24
-
Since the lower limit has been internally set, the setting value of 3 % or less is recognized as 3%. More Details >>
- No:20976
- Release Date:2018/08/22 16:25
-
When the online auto tuning (magnetic field observer) is enabled, the monitoring accuracy is ± 10%. More Details >>
- No:20981
- Release Date:2018/08/22 16:25
-
The day of the week is automatically determined from the data of year, month, and day. More Details >>
- No:20997
- Release Date:2018/08/22 16:25
-
If Pr.361 = 0, the second terminal can be used as the line speed command when X114 is ON, and as the frequency setting value when X114 is OFF. If Pr.361 = 3,... More Details >>
- No:20891
- Release Date:2018/08/22 16:24
-
UVT will occur when reactor is not connected. Always connect a reactor that matches the motor capacity. More Details >>
- No:20978
- Release Date:2018/08/22 16:25
-
Combination of the FR-A800 and MM-BF
Select the models so that "MM - BF rated current value × 1.05 < FR-A820 rated output current value". More Details >>
- No:21000
- Release Date:2018/08/22 16:25
-
Fuses are not required as peripheral devices for the FR-A802, which has internal fuses. More Details >>
- No:21019
- Release Date:2018/08/22 16:25
-
Yes, the current response is also improved at the same rate. More Details >>
- No:21079
- Release Date:2018/08/22 16:25
-
Positioning is available by inputting pulse trains to the terminal JOG, same as the A700 series. More Details >>
- No:21104
- Release Date:2018/08/22 16:25