FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F800
FAQ
Keyword Search
FAQ within [ FREQROL-F800 ]
-
The undervoltage warning of the inverter is judged based on the voltage of the main circuit as follows. Power failure only at the main circuit: Output an und... More Details >>
- No:20853
- Release Date:2018/08/22 16:24
-
SW1DND-FRC2 (FR Configurator2)
Check the setting value of Pr.414 (PLC function operation selection) and if the initial value: 0 (PLC function disabled) is set, set "1" or "2" and enable th... More Details >>
- No:21080
- Release Date:2018/08/22 16:25
-
The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>
- No:20859
- Release Date:2018/08/22 16:24
-
It can be used in terms of the specifications. However, it is recommended to update the reactor and inverter at the same time because the DC reactor was manu... More Details >>
- No:21017
- Release Date:2018/08/22 16:25
-
It cannot be connected. When using DU08, connect it to the PU connector. More Details >>
- No:21111
- Release Date:2018/08/22 16:25
-
The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>
- No:20995
- Release Date:2018/08/22 16:25
-
The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>
- No:20994
- Release Date:2018/08/22 16:25
-
The FR-PU07(BB) can be used with some restrictions.* The major restrictions are as follows. - Pr.1000 or later cannot be set. - Alarms or warnings that are a... More Details >>
- No:21119
- Release Date:2018/08/22 16:26
-
No. (Using the copy function causes an error.) Use the FR-DU08 when performing the copy function of the operation panel. More Details >>
- No:21118
- Release Date:2018/08/22 16:26
-
The conventional plug-in option (FR-A7[][]) cannot be used. Use the dedicated plug-in option (FR-A8[][]). More Details >>
- No:21114
- Release Date:2018/08/22 16:25
1-10 of Total 89