Combination of the FR-F800 and MM-EFS
Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>
- No:20820
- Release Date:2018/08/22 16:24
-
Up to 64 (slave stations). The number of connectable units differs depending on the master station. More Details >>
- No:20857
- Release Date:2018/08/22 16:24
-
Residual voltage at the output shutoff
The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>
- No:20906
- Release Date:2018/08/22 16:25
-
Yes, the current is limited under the PM sensorless control. More Details >>
- No:20936
- Release Date:2018/08/22 16:25
-
The number of timer points is 16 for the high speed and low speed in total. More Details >>
- No:21056
- Release Date:2018/08/22 16:25
-
Under Advanced magnetic flux vector control or PM motor control, measuring motor constants automatically enables optimal operation of motors even when motor ... More Details >>
- No:21071
- Release Date:2018/08/22 16:25
-
The 800 series supports the multiple rating. Thus, the rated current of the corresponding motor is 40% or higher of the inverter rated current. (Using a moto... More Details >>
- No:21085
- Release Date:2018/08/22 16:25
-
Yes, it can like the standard product. More Details >>
- No:20880
- Release Date:2018/08/22 16:24
-
When it is required to keep the safety of the inverter and the system against unauthorized access from external devices via the network, take countermeasures... More Details >>
- No:20883
- Release Date:2018/08/22 16:24
-
DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>
- No:20905
- Release Date:2018/08/22 16:25