Load characteristics fault detection
It is based on the motor rated torque. More Details >>
- No:20895
- Release Date:2018/08/22 16:24
-
Power is supplied only to the control power supply, and thus this enables communication, parameter setting through the operation panel or an USB memory devic... More Details >>
- No:21097
- Release Date:2018/08/22 16:25
-
It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>
- No:20899
- Release Date:2018/08/22 16:24
-
By setting the operating condition, such as load level and surrounding air temperature, according to the application, the inverter capacity may be lowered co... More Details >>
- No:21101
- Release Date:2018/08/22 16:25
-
Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>
- No:21053
- Release Date:2018/08/22 16:25
-
There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>
- No:20884
- Release Date:2018/08/22 16:24
-
In the FR-A800/F800, the restriction on the wiring length of the shielded cable is eliminated. The wiring length is up to 500 m as is the case with the unshi... More Details >>
- No:21089
- Release Date:2018/08/22 16:25
-
Yes, it can like the standard product. More Details >>
- No:20880
- Release Date:2018/08/22 16:24
-
Combination of the FR-F800 and FR-A8TAT
Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>
- No:20841
- Release Date:2018/08/22 16:24
-
No, the MT-BU5 is not available Use the FR-BU2 instead. More Details >>
- No:21076
- Release Date:2018/08/22 16:25