11-20 of Total 89

prev 2 / 9page next
  • Load characteristics fault detection

    Only the V/F control is related with Pr.56. The motor torque is calculated from the current value (not Pr.56) and motor constant. For the V/F control, it is ... More Details >>

    • No:20893
    • Release Date:2018/08/22 16:24
  • PLC function

    The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>

    • No:21048
    • Release Date:2018/08/22 16:25
  • PLC function

    It is 1 s interval. More Details >>

    • No:21055
    • Release Date:2018/08/22 16:25
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>

    • No:20884
    • Release Date:2018/08/22 16:24
  • Control terminal block

    It is available if the option FR-A8TAT (Control circuit terminal block intercompatibility attachment) is installed. (Some functions have restrictions. For th... More Details >>

    • No:21087
    • Release Date:2018/08/22 16:25
  • FR-A800

    No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>

    • No:20878
    • Release Date:2018/08/22 16:24
  • FR-A800-E

    Yes, it can like the standard product. More Details >>

    • No:20880
    • Release Date:2018/08/22 16:24
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25
  • Output signal

    The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>

    • No:20995
    • Release Date:2018/08/22 16:25

11-20 of Total 89