FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F800
FAQ
Keyword Search
FAQ within [ FREQROL-F800 ]
-
No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
- No:20878
- Release Date:2018/08/22 16:24
-
There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>
- No:20884
- Release Date:2018/08/22 16:24
-
Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>
- No:20904
- Release Date:2018/08/22 16:25
-
Communication specifications for connection of multiple inverters
Use the RS485 terminal for the multiple communication of the A series/F series inverters.* Communication with the PU connector is only one-to-one connection. More Details >>
- No:20998
- Release Date:2018/08/22 16:25
-
They can be compliant by connecting an optional DC reactor (FR-HEL). (A capacitive filter and common mode choke are built in (the common mode choke is provid... More Details >>
- No:21117
- Release Date:2018/08/22 16:26
-
Yes, it can like the standard product. More Details >>
- No:20880
- Release Date:2018/08/22 16:24
-
It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>
- No:20881
- Release Date:2018/08/22 16:24
-
Carrier frequency automatic reducing function
The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>
- No:20903
- Release Date:2018/08/22 16:25
-
The country in which the product is manufactured is described on the rating plate as MADE IN JAPAN or MADE IN CHINA. More Details >>
- No:20956
- Release Date:2018/08/22 16:25
-
Parameter copy to the USB memory
Yes. Parameters can be read except during an inverter reset or when the password function is set. More Details >>
- No:20961
- Release Date:2018/08/22 16:25
11-20 of Total 89