Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F800 ]

11-20 of Total 89

prev 2 / 9page next
  • FR-A800-E

    There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>

    • No:20884
    • Release Date:2018/08/22 16:24
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • Residual voltage at the output shutoff

    The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>

    • No:20906
    • Release Date:2018/08/22 16:25
  • FR-F800

    Yes, the current is limited under the PM sensorless control. More Details >>

    • No:20936
    • Release Date:2018/08/22 16:25
  • Storage area

    The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>

    • No:20958
    • Release Date:2018/08/22 16:25
  • FR-F800

    No, it isn't. Use the multiple rating (LD, SLD) of the FR-A800. More Details >>

    • No:20972
    • Release Date:2018/08/22 16:25
  • Radio Act

    The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>

    • No:20994
    • Release Date:2018/08/22 16:25
  • PLC function

    The maximum values are kept. The values are not cleared to zero. More Details >>

    • No:21015
    • Release Date:2018/08/22 16:25

11-20 of Total 89