  • Error at USB parameter copy

    This error occurs when the parameter file is broken. More Details >>

    • No:20937
    • Release Date:2018/08/22 16:25
  • Terminal response time

    It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>

    • No:20899
    • Release Date:2018/08/22 16:24
  • Front cover

    Parts arrangement is available. Consult with your sales agent. More Details >>

    • No:21012
    • Release Date:2018/08/22 16:25
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • PLC function

    The number of timer points is 16 for the high speed and low speed in total. More Details >>

    • No:21056
    • Release Date:2018/08/22 16:25
  • Frequency search of the FR-A800/FR-F800

    DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>

    • No:20831
    • Release Date:2018/08/22 16:24
  • Optimum excitation control

    For the FR-F800 series, in addition to the conventional Optimum excitation control, Advanced optimum excitation control with the improved starting torque is ... More Details >>

    • No:21072
    • Release Date:2018/08/22 16:25
  • PLC function

    No. To set the PLC function, FR Configurator2 is required. (However, the setting cannot be configured with the trial version.) More Details >>

    • No:21102
    • Release Date:2018/08/22 16:25
  • Europe EMC Directive compliance

    By turning ON the connector of the built-in filter, the inverter can be compliant with EMC Directive (EN 61800-3 2nd Environment C3) alone. More Details >>

    • No:21116
    • Release Date:2018/08/22 16:26
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25