FAQ within [ FREQROL-F800 ]
-
The FR-PU07(BB) can be used with some restrictions.* The major restrictions are as follows. - Pr.1000 or later cannot be set. - Alarms or warnings that are a... More Details >>
- No:21119
- Release Date:2018/08/22 16:26
-
The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>
- No:21048
- Release Date:2018/08/22 16:25
-
The number of terminals: There are the same input terminals as F700P and the following terminals (4 points) are added. Safety: SI1, SI2, SIC 24 V power suppl... More Details >>
- No:21070
- Release Date:2018/08/22 16:25
-
The trace data is stored in the built-in RAM of the inverter and deleted when the power is turned OFF or the inverter is reset. The data can be held with any... More Details >>
- No:21078
- Release Date:2018/08/22 16:25
-
No, it cannot. The standard operation panel (FR-DU08) can be connected to the face of the board by using the FR-ADP (operation panel connection connector) an... More Details >>
- No:20898
- Release Date:2018/08/22 16:24
-
Carrier frequency automatic reducing function
The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>
- No:20903
- Release Date:2018/08/22 16:25
-
Life measurement of the main circuit capacitor
No. Turn OFF and ON both main circuit and control circuit. More Details >>
- No:20999
- Release Date:2018/08/22 16:25
-
Approximately 2 years when the FR-LU08 is not energized and the real-time clock function is enabled. More Details >>
- No:21084
- Release Date:2018/08/22 16:25
-
The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>
- No:20859
- Release Date:2018/08/22 16:24
-
Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>
- No:20904
- Release Date:2018/08/22 16:25
21-30 of Total 89