Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F800 ]

21-30 of Total 89

prev 3 / 9page next
  • FR-A800-E

    The direct connection with the inverter like the standard model, and the connection via the GOT and relay station (programmable controller) are available. On... More Details >>

    • No:20879
    • Release Date:2018/08/22 16:24
  • CC-Link IE Field Basic

    Only the FR-A800/F800-E series is supported by CC-Link IE Field Basic. (As of March 2017) The FR-A800-GF and FR-A8NCE supported by CC-Link IE Field are not s... More Details >>

    • No:20858
    • Release Date:2018/08/22 16:24
  • Terminal response time

    It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>

    • No:20899
    • Release Date:2018/08/22 16:24
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • PLC function

    The number of timer points is 16 for the high speed and low speed in total. More Details >>

    • No:21056
    • Release Date:2018/08/22 16:25
  • Trace data

    The trace data is stored in the built-in RAM of the inverter and deleted when the power is turned OFF or the inverter is reset. The data can be held with any... More Details >>

    • No:21078
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    Yes, it can like the standard product. More Details >>

    • No:20880
    • Release Date:2018/08/22 16:24
  • Combination of the FR-F800 and FR-A8TAT

    Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>

    • No:20841
    • Release Date:2018/08/22 16:24
  • Residual voltage at the output shutoff

    The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>

    • No:20906
    • Release Date:2018/08/22 16:25