FAQ within [ FREQROL-F800 ]
-
For the FR-F700P, only dedicated IPM motor (MM-EFS, MM-THE4) can be driven. For the FR-F800, the name is different because PM motors manufactured by other co... More Details >>
- No:21061
- Release Date:2018/08/22 16:25
-
No. (Using the copy function causes an error.) Use the FR-DU08 when performing the copy function of the operation panel. More Details >>
- No:21118
- Release Date:2018/08/22 16:26
-
Yes, it does, however, it does not acquire the certification of the BACnet association standard. More Details >>
- No:20863
- Release Date:2018/08/22 16:24
-
It is 1 s interval. More Details >>
- No:21055
- Release Date:2018/08/22 16:25
-
The number of timer points is 16 for the high speed and low speed in total. More Details >>
- No:21056
- Release Date:2018/08/22 16:25
-
No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
- No:20878
- Release Date:2018/08/22 16:24
-
Residual voltage at the output shutoff
The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>
- No:20906
- Release Date:2018/08/22 16:25
-
LD is not supported, however, SLD is supported. More Details >>
- No:21054
- Release Date:2018/08/22 16:25
-
By setting the operating condition, such as load level and surrounding air temperature, according to the application, the inverter capacity may be lowered co... More Details >>
- No:21101
- Release Date:2018/08/22 16:25
-
Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>
- No:20904
- Release Date:2018/08/22 16:25