  • PLC function

    SD1148 can turn ON multiple bits such as STF and RH simultaneously. SM turns ON bits individually. When SD1148 is H5, it is same as when SM1200 (STF) and SM1... More Details >>

    • No:21057
    • Release Date:2018/08/22 16:25
  • PLC function

    When Pr.414 is set to "1" and Pr.388 is set to "0", the PLC function is not enabled unless both the SQ signal from communication and the SQ signal from the e... More Details >>

    • No:21073
    • Release Date:2018/08/22 16:25
  • Europe EMC Directive compliance

    By turning ON the connector of the built-in filter, the inverter can be compliant with EMC Directive (EN 61800-3 2nd Environment C3) alone. More Details >>

    • No:21116
    • Release Date:2018/08/22 16:26
  • Compliance with Electric/Machinery Facility Common Specifications of the Ministry of Land, Infrastructure, Transport and Tourism of Japan

    They can be compliant by connecting an optional DC reactor (FR-HEL). (A capacitive filter and common mode choke are built in (the common mode choke is provid... More Details >>

    • No:21117
    • Release Date:2018/08/22 16:26
  • Built-in PLC function

    The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>

    • No:20859
    • Release Date:2018/08/22 16:24
  • FR-A800-E

    When it is required to keep the safety of the inverter and the system against unauthorized access from external devices via the network, take countermeasures... More Details >>

    • No:20883
    • Release Date:2018/08/22 16:24
  • FR-A800-E

    There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>

    • No:20884
    • Release Date:2018/08/22 16:24
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • PLC function

    It is 1 s interval. More Details >>

    • No:21055
    • Release Date:2018/08/22 16:25
  • PLC function

    The number of timer points is 16 for the high speed and low speed in total. More Details >>

    • No:21056
    • Release Date:2018/08/22 16:25