No, it cannot. The standard operation panel (FR-DU08) can be connected to the face of the board by using the FR-ADP (operation panel connection connector) an... More Details >>
- No:20898
- Release Date:2018/08/22 16:24
-
The number of terminals: There are the same input terminals as F700P and the following terminals (4 points) are added. Safety: SI1, SI2, SIC 24 V power suppl... More Details >>
- No:21070
- Release Date:2018/08/22 16:25
-
The trace data is stored in the built-in RAM of the inverter and deleted when the power is turned OFF or the inverter is reset. The data can be held with any... More Details >>
- No:21078
- Release Date:2018/08/22 16:25
-
Combination of the FR-F800 and MM-EFS
Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>
- No:20820
- Release Date:2018/08/22 16:24
-
It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>
- No:20881
- Release Date:2018/08/22 16:24
-
It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>
- No:20899
- Release Date:2018/08/22 16:24
-
Carrier frequency automatic reducing function
The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>
- No:20903
- Release Date:2018/08/22 16:25
-
Life measurement of the main circuit capacitor
No. Turn OFF and ON both main circuit and control circuit. More Details >>
- No:20999
- Release Date:2018/08/22 16:25
-
Approximately 2 years when the FR-LU08 is not energized and the real-time clock function is enabled. More Details >>
- No:21084
- Release Date:2018/08/22 16:25
-
The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>