  • MT-BU5

    No, the MT-BU5 is not available Use the FR-BU2 instead. More Details >>

    • No:21076
    • Release Date:2018/08/22 16:25
  • FR-A800/FR-F800

    When only the main circuit input power supply is cut off with the MC (when the power supply shutoff time is long), the main circuit undervoltage or instantan... More Details >>

    • No:20833
    • Release Date:2018/08/22 16:24
  • 24 VDC power supply

    Power is supplied only to the control power supply, and thus this enables communication, parameter setting through the operation panel or an USB memory devic... More Details >>

    • No:21097
    • Release Date:2018/08/22 16:25
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25
  • DC reactor

    It can be used since the specifications are the same. Note that the warranty period and expected lifespan for the A700/F700P are inherited. More Details >>

    • No:21092
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>

    • No:20882
    • Release Date:2018/08/22 16:24
  • Control terminal block

    It is available if the option FR-A8TAT (Control circuit terminal block intercompatibility attachment) is installed. (Some functions have restrictions. For th... More Details >>

    • No:21087
    • Release Date:2018/08/22 16:25
  • Installation necessity of a DC reactor

    A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>

    • No:21077
    • Release Date:2018/08/22 16:25
  • Residual voltage at the output shutoff

    The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>

    • No:20906
    • Release Date:2018/08/22 16:25
  • Multiple rating

    By setting the operating condition, such as load level and surrounding air temperature, according to the application, the inverter capacity may be lowered co... More Details >>