    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • Storage area

    The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>

    • No:20958
    • Release Date:2018/08/22 16:25
  • PM motor control

    For the FR-F700P, only dedicated IPM motor (MM-EFS, MM-THE4) can be driven. For the FR-F800, the name is different because PM motors manufactured by other co... More Details >>

    • No:21061
    • Release Date:2018/08/22 16:25
  • Optimum excitation control

    For the FR-F800 series, in addition to the conventional Optimum excitation control, Advanced optimum excitation control with the improved starting torque is ... More Details >>

    • No:21072
    • Release Date:2018/08/22 16:25
  • FR-A800-E

    The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>

    • No:20882
    • Release Date:2018/08/22 16:24
  • FR-A800-E

    When it is required to keep the safety of the inverter and the system against unauthorized access from external devices via the network, take countermeasures... More Details >>

    • No:20883
    • Release Date:2018/08/22 16:24
  • Load characteristics fault detection

    Only the V/F control is related with Pr.56. The motor torque is calculated from the current value (not Pr.56) and motor constant. For the V/F control, it is ... More Details >>

    • No:20893
    • Release Date:2018/08/22 16:24
  • Error at USB parameter copy

    This error occurs when the parameter file is broken. More Details >>

    • No:20937
    • Release Date:2018/08/22 16:25
  • Gain adjustment under the speed control

    Since the lower limit has been internally set, 3% or less is recognized as 3%. More Details >>

    • No:21016
    • Release Date:2018/08/22 16:25
  • 24 VDC power supply

    Do not remove the jumper of the R1 and S1 when inputting the control circuit power supply from the external 24 V power supply (connecting across the terminal... More Details >>

    • No:21074
    • Release Date:2018/08/22 16:25