  • Safety stop function

    Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>

    • No:21053
    • Release Date:2018/08/22 16:25
  • FR-A800/FR-F800

    When only the main circuit input power supply is cut off with the MC (when the power supply shutoff time is long), the main circuit undervoltage or instantan... More Details >>

    • No:20833
    • Release Date:2018/08/22 16:24
  • PLC function

    The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>

    • No:21048
    • Release Date:2018/08/22 16:25
  • Model

    LD is not supported, however, SLD is supported. More Details >>

    • No:21054
    • Release Date:2018/08/22 16:25
  • PLC function

    It is 1 s interval. More Details >>

    • No:21055
    • Release Date:2018/08/22 16:25
  • FR-A800/FR-F800

    It is 30 clicks the FR-A800/FR-F800. More Details >>

    • No:20811
    • Release Date:2018/08/22 16:24
  • Reduced impact restart

    Until now the DC has been applied to perform the frequency search. When Pr.162 = 3 or 13, the impact is reduced by detecting the phase and performing the sea... More Details >>

    • No:20904
    • Release Date:2018/08/22 16:25
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • PLC function

    When Pr.414 is set to "1" and Pr.388 is set to "0", the PLC function is not enabled unless both the SQ signal from communication and the SQ signal from the e... More Details >>

    • No:21073
    • Release Date:2018/08/22 16:25
  • PLC function

    The maximum values are kept. The values are not cleared to zero. More Details >>

    • No:21015
    • Release Date:2018/08/22 16:25

31-40 of Total 89