FAQ within [ FREQROL-F800 ]

31-40 of Total 89

prev 4 / 9page next
  • FR-F800

    No, it isn't. Use the multiple rating (LD, SLD) of the FR-A800. More Details >>

    • No:20972
    • Release Date:2018/08/22 16:25
  • Front cover

    Parts arrangement is available. Consult with your sales agent. More Details >>

    • No:21012
    • Release Date:2018/08/22 16:25
  • EMC filter

    A capacitive filter and common mode choke are built in. (A common mode choke is built in only for the 55K or lower.) Use a connector for whether to turn ON o... More Details >>

    • No:21094
    • Release Date:2018/08/22 16:25
  • Multiple rating

    By setting the operating condition, such as load level and surrounding air temperature, according to the application, the inverter capacity may be lowered co... More Details >>

    • No:21101
    • Release Date:2018/08/22 16:25
  • FR-PA07

    No, it cannot. The standard operation panel (FR-DU08) can be connected to the face of the board by using the FR-ADP (operation panel connection connector) an... More Details >>

    • No:20898
    • Release Date:2018/08/22 16:24
  • CC-Link option

    Yes, they are the same. More Details >>

    • No:21010
    • Release Date:2018/08/22 16:25
  • Europe EMC Directive compliance

    By turning ON the connector of the built-in filter, the inverter can be compliant with EMC Directive (EN 61800-3 2nd Environment C3) alone. More Details >>

    • No:21116
    • Release Date:2018/08/22 16:26
  • FR-A800

    No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>

    • No:20878
    • Release Date:2018/08/22 16:24
  • Terminal response time

    It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>

    • No:20899
    • Release Date:2018/08/22 16:24
  • FR-A8AX/A8AY

    For the FR-A700/F700, the hook is cut off for the wiring due to restrictions on the structure. These restrictions are eliminated for the FR-A800/F800. More Details >>

    • No:21051
    • Release Date:2018/08/22 16:25