FAQ within [ FREQROL-F800 ]
-
The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>
- No:20882
- Release Date:2018/08/22 16:24
-
If using an inverter with capacity of 75K or higher, or motor with capacity of 75 kW or higher, always select and install the inverter based on the capacity ... More Details >>
- No:21112
- Release Date:2018/08/22 16:25
-
Frequency search of the FR-A800/FR-F800
DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>
- No:20831
- Release Date:2018/08/22 16:24
-
The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>
- No:20859
- Release Date:2018/08/22 16:24
-
Residual voltage at the output shutoff
The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>
- No:20906
- Release Date:2018/08/22 16:25
-
Parameter copy to the USB memory
Yes. Parameters can be read except during an inverter reset or when the password function is set. More Details >>
- No:20961
- Release Date:2018/08/22 16:25
-
Combination of the FR-F800 and MM-EFS
Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>
- No:20820
- Release Date:2018/08/22 16:24
-
It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>
- No:20899
- Release Date:2018/08/22 16:24
-
The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>
- No:20958
- Release Date:2018/08/22 16:25
-
The conventional plug-in option (FR-A7[][]) cannot be used. Use the dedicated plug-in option (FR-A8[][]). More Details >>
- No:21114
- Release Date:2018/08/22 16:25