  • Control power supply

    Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation. Therefore, the separate power supply canno... More Details >>

    • No:21018
    • Release Date:2018/08/22 16:25
  • PLC function

    The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>

    • No:21048
    • Release Date:2018/08/22 16:25
  • Safety stop function

    Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>

    • No:21053
    • Release Date:2018/08/22 16:25
  • Combination of the FR-F800 and FR-A8TAT

    Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>

    • No:20841
    • Release Date:2018/08/22 16:24
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25
  • Frequency search

    DC application method (Pr.162 = 0 or 10): 4 Hz or lower is regarded as 0 Hz. AC application method (Pr.162 = 3 or 13): It is not defined since it depends on ... More Details >>

    • No:20905
    • Release Date:2018/08/22 16:25
  • Parameter copy to the USB memory

    Yes. Parameters can be read except during an inverter reset or when the password function is set. More Details >>

    • No:20961
    • Release Date:2018/08/22 16:25
  • FR-A800/FR-F800

    It is 30 clicks the FR-A800/FR-F800. More Details >>

    • No:20811
    • Release Date:2018/08/22 16:24
  • FR-A800/FR-F800

    When only the main circuit input power supply is cut off with the MC (when the power supply shutoff time is long), the main circuit undervoltage or instantan... More Details >>

    • No:20833
    • Release Date:2018/08/22 16:24
  • CC-Link IE Field Basic

    Only the FR-A800/F800-E series is supported by CC-Link IE Field Basic. (As of March 2017) The FR-A800-GF and FR-A8NCE supported by CC-Link IE Field are not s... More Details >>

    • No:20858
    • Release Date:2018/08/22 16:24