FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F800
FAQ
Keyword Search
FAQ within [ FREQROL-F800 ]
-
They can be compliant by connecting an optional DC reactor (FR-HEL). (A capacitive filter and common mode choke are built in (the common mode choke is provid... More Details >>
- No:21117
- Release Date:2018/08/22 16:26
-
Frequency search of the FR-A800/FR-F800
DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>
- No:20831
- Release Date:2018/08/22 16:24
-
Setting values of the FR-F800 when replaced with the FR-F400
The performance and noise countermeasure were improved and the initial value is set to "8". Try with the initial value "2" first. If the noise is distracting... More Details >>
- No:20808
- Release Date:2018/08/22 16:24
-
Carrier frequency automatic reducing function
The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>
- No:20903
- Release Date:2018/08/22 16:25
-
Residual voltage at the output shutoff
The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>
- No:20906
- Release Date:2018/08/22 16:25
-
Power is supplied only to the control power supply, and thus this enables communication, parameter setting through the operation panel or an USB memory devic... More Details >>
- No:21097
- Release Date:2018/08/22 16:25
-
Combination of the FR-F800 and MM-EFS
Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>
- No:20820
- Release Date:2018/08/22 16:24
-
For the FR-F800 series, in addition to the conventional Optimum excitation control, Advanced optimum excitation control with the improved starting torque is ... More Details >>
- No:21072
- Release Date:2018/08/22 16:25
-
Load characteristics fault detection
Only the V/F control is related with Pr.56. The motor torque is calculated from the current value (not Pr.56) and motor constant. For the V/F control, it is ... More Details >>
- No:20893
- Release Date:2018/08/22 16:24
-
The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>
- No:20882
- Release Date:2018/08/22 16:24
51-60 of Total 89