  • Communication specifications for connection of multiple inverters

    Use the RS485 terminal for the multiple communication of the A series/F series inverters.* Communication with the PU connector is only one-to-one connection. More Details >>

    • No:20998
    • Release Date:2018/08/22 16:25
  • PLC function

    The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>

    • No:21048
    • Release Date:2018/08/22 16:25
  • Safety stop function

    Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>

    • No:21053
    • Release Date:2018/08/22 16:25
  • PLC function

    SD1148 can turn ON multiple bits such as STF and RH simultaneously. SM turns ON bits individually. When SD1148 is H5, it is same as when SM1200 (STF) and SM1... More Details >>

    • No:21057
    • Release Date:2018/08/22 16:25
  • Operation panel

    If the operation panel has not been operated for the time set in Pr.1048 Display-off waiting time, the display-off mode is enabled and the "MON" LED blinks s... More Details >>

    • No:21075
    • Release Date:2018/08/22 16:25
  • USB

    The mini B connector is used for connecting with FR Configurator2. A USB memory device can be connected to the A connector (host) to save parameters or trace... More Details >>

    • No:21095
    • Release Date:2018/08/22 16:25
  • PLC function

    No. To set the PLC function, FR Configurator2 is required. (However, the setting cannot be configured with the trial version.) More Details >>

    • No:21102
    • Release Date:2018/08/22 16:25
  • PLC function

    The processing speed, scan time, and others are slower than those of the programmable controllers. There are some restrictions in the number of I/O points, p... More Details >>

    • No:21103
    • Release Date:2018/08/22 16:25
  • Compliance with Electric/Machinery Facility Common Specifications of the Ministry of Land, Infrastructure, Transport and Tourism of Japan

    They can be compliant by connecting an optional DC reactor (FR-HEL). (A capacitive filter and common mode choke are built in (the common mode choke is provid... More Details >>

    • No:21117
    • Release Date:2018/08/22 16:26
  • FR-A800/FR-F800

    When only the main circuit input power supply is cut off with the MC (when the power supply shutoff time is long), the main circuit undervoltage or instantan... More Details >>

    • No:20833
    • Release Date:2018/08/22 16:24