  • FR-PU07

    No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>

    • No:21081
    • Release Date:2018/08/22 16:25
  • Combination of the FR-F800 and FR-A8TAT

    Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>

    • No:20841
    • Release Date:2018/08/22 16:24
  • 24 VDC power supply

    Do not remove the jumper of the R1 and S1 when inputting the control circuit power supply from the external 24 V power supply (connecting across the terminal... More Details >>

    • No:21074
    • Release Date:2018/08/22 16:25
  • DC reactor

    It can be used since the specifications are the same. Note that the warranty period and expected lifespan for the A700/F700P are inherited. More Details >>

    • No:21092
    • Release Date:2018/08/22 16:25
  • Installation necessity of a DC reactor

    A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>

    • No:21077
    • Release Date:2018/08/22 16:25
  • EMC filter

    A capacitive filter and common mode choke are built in. (A common mode choke is built in only for the 55K or lower.) Use a connector for whether to turn ON o... More Details >>

    • No:21094
    • Release Date:2018/08/22 16:25
  • Multiple rating

    By setting the operating condition, such as load level and surrounding air temperature, according to the application, the inverter capacity may be lowered co... More Details >>

    • No:21101
    • Release Date:2018/08/22 16:25
  • CC-Link option

    Yes, they are the same. More Details >>

    • No:21010
    • Release Date:2018/08/22 16:25
  • Setting values of the FR-F800 when replaced with the FR-F400

    The performance and noise countermeasure were improved and the initial value is set to "8". Try with the initial value "2" first. If the noise is distracting... More Details >>

    • No:20808
    • Release Date:2018/08/22 16:24
  • Life measurement of the main circuit capacitor

    No. Turn OFF and ON both main circuit and control circuit. More Details >>