Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F800 ]

71-80 of Total 89

prev 8 / 9page next
  • Combination of the FR-F800 and MM-EFS

    Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>

    • No:20820
    • Release Date:2018/08/22 16:24
  • FR-A800/FR-F800

    It is 30 clicks the FR-A800/FR-F800. More Details >>

    • No:20811
    • Release Date:2018/08/22 16:24
  • Terminal response time

    It is 2 to 3 ms. By setting Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the FR-A700 can be compatible with the response of the t... More Details >>

    • No:20899
    • Release Date:2018/08/22 16:24
  • FR-A800-E

    It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>

    • No:20881
    • Release Date:2018/08/22 16:24
  • Operation panel

    If the operation panel has not been operated for the time set in Pr.1048 Display-off waiting time, the display-off mode is enabled and the "MON" LED blinks s... More Details >>

    • No:21075
    • Release Date:2018/08/22 16:25
  • Control power supply

    Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation. Therefore, the separate power supply canno... More Details >>

    • No:21018
    • Release Date:2018/08/22 16:25
  • Error at USB parameter copy

    This error occurs when the parameter file is broken. More Details >>

    • No:20937
    • Release Date:2018/08/22 16:25
  • FR-F800

    Yes, the current is limited under the PM sensorless control. More Details >>

    • No:20936
    • Release Date:2018/08/22 16:25
  • FR-A800

    No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>

    • No:20878
    • Release Date:2018/08/22 16:24
  • PM motor control

    For the FR-F700P, only dedicated IPM motor (MM-EFS, MM-THE4) can be driven. For the FR-F800, the name is different because PM motors manufactured by other co... More Details >>

    • No:21061
    • Release Date:2018/08/22 16:25

71-80 of Total 89