FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F800
FAQ
Keyword Search
FAQ within [ FREQROL-F800 ]
-
The undervoltage warning of the inverter is judged based on the voltage of the main circuit as follows. Power failure only at the main circuit: Output an und... More Details >>
- No:20853
- Release Date:2018/08/22 16:24
-
Parameter copy to the USB memory
No. Writing is not available when the model is different. Writing the parameter copy file using a USB memory device is available only for the same models. Ot... More Details >>
- No:21014
- Release Date:2018/08/22 16:25
-
SD1148 can turn ON multiple bits such as STF and RH simultaneously. SM turns ON bits individually. When SD1148 is H5, it is same as when SM1200 (STF) and SM1... More Details >>
- No:21057
- Release Date:2018/08/22 16:25
-
A radio noise filter can be used with a built-in filter. More Details >>
- No:21113
- Release Date:2018/08/22 16:25
-
In the FR-A800/F800, the restriction on the wiring length of the shielded cable is eliminated. The wiring length is up to 500 m as is the case with the unshi... More Details >>
- No:21089
- Release Date:2018/08/22 16:25
-
If using an inverter with capacity of 75K or higher, or motor with capacity of 75 kW or higher, always select and install the inverter based on the capacity ... More Details >>
- No:21112
- Release Date:2018/08/22 16:25
-
The FR-PU07(BB) can be used with some restrictions.* The major restrictions are as follows. - Pr.1000 or later cannot be set. - Alarms or warnings that are a... More Details >>
- No:21119
- Release Date:2018/08/22 16:26
-
SW1DND-FRC2 (FR Configurator2)
Check the setting value of Pr.414 (PLC function operation selection) and if the initial value: 0 (PLC function disabled) is set, set "1" or "2" and enable th... More Details >>
- No:21080
- Release Date:2018/08/22 16:25
-
Installation necessity of a DC reactor
A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>
- No:21077
- Release Date:2018/08/22 16:25
-
If the operation panel has not been operated for the time set in Pr.1048 Display-off waiting time, the display-off mode is enabled and the "MON" LED blinks s... More Details >>
- No:21075
- Release Date:2018/08/22 16:25
1-10 of Total 89