FAQ within [ FREQROL-E700 ]

91-100 of Total 394

prev 10 / 40page next
  • Running frequency setting

    Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>

    • No:21880
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    1. You can set the station number.However, you can only connect a single personal computer to a single inverter.2. You can set communication by choosing Tool... More Details >>

    • No:21882
    • Release Date:2018/08/22 16:29
  • Reverse operation

    Reverse operation is enabled by changing the setting of Pr.40. More Details >>

    • No:21287
    • Release Date:2018/08/22 16:26
  • CC-Link

    The FR-A7NC is required. ("FR-A7NC-E kit" for the FR-E700 series. The FR-E700-NC CC-Link communication type does not require an option.) More Details >>

    • No:21668
    • Release Date:2018/08/22 16:28
  • Motor with an attached brake

    Connecting it causes no problem. More Details >>

    • No:21671
    • Release Date:2018/08/22 16:28
  • CC-Link station number setting

    Change the setting in the PU operation mode.   More Details >>

    • No:21747
    • Release Date:2018/08/22 16:29
  • Operation panel LED

    No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>

    • No:21776
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.338 (Operation command source) to "1" (external terminal).Set Pr.339 (Speed command source) to "0" (communication).Check the setting of Pr.79 for oper... More Details >>

    • No:21869
    • Release Date:2018/08/22 16:29
  • CC-Link

    For the inverter, the option card FR-A7NC is necessary.   More Details >>

    • No:21897
    • Release Date:2018/08/22 16:29
  • Electronic thermal O/L relay

    Check that the correct rated motor current is set in Pr.9 (Electronic thermal O/L relay). No parameter is available for setting the operation time of the ele... More Details >>