FAQ within [ FREQROL-E700 ]

121-130 of Total 393

prev 13 / 40page next
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29
  • External operation

    The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>

    • No:21849
    • Release Date:2018/08/22 16:29
  • FR-PA07

    The mounting screw is not supplied. The mounting screw is supplied with the operation panel. Open the screw hole according to the dimension. (The M3 screw is... More Details >>

    • No:21361
    • Release Date:2018/08/22 16:27
  • Frequency setting

    You can set the running frequency up to 400 Hz.It depends on the specifications of the motor used whether or not operation with a frequency of 120 Hz or high... More Details >>

    • No:21738
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it.   More Details >>

    • No:21711
    • Release Date:2018/08/22 16:29
  • FR-PA07

    Since the multi-speed is given a higher priority, the setting by the setting dial is not enabled unless all of the multi-speed signals are OFF. More Details >>

    • No:21302
    • Release Date:2018/08/22 16:26
  • Operation stop, frequency setting

    Set Pr.79 (Operation mode) to "1" (PU operation mode).  More Details >>

    • No:21819
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29