FAQ within [ FREQROL-E700 ]

131-140 of Total 393

prev 14 / 40page next
  • Frequency setting

    You cannot calibrate the frequency around the middle of the current input range.The inverter determines the top and bottom points in the bias/gain adjustment... More Details >>

    • No:21736
    • Release Date:2018/08/22 16:29
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • CC-Link

    1. You can reset the inverter from an external terminal.You can do it without regard to the setting of Pr.338 (Communication operation command source) and Pr... More Details >>

    • No:21837
    • Release Date:2018/08/22 16:29
  • CC-Link

    Connect the wire to the optional FR-A7NC's terminal block. (The terminal block is detachable.) More Details >>

    • No:21875
    • Release Date:2018/08/22 16:29
  • Parameter read

    By setting Pr.160 (User group read selection ("Extended function display selection" for D700)) to "0", all the parameters can be read. More Details >>

    • No:21262
    • Release Date:2018/08/22 16:26
  • Installation of options

    Use the digital output/additional analog output FR-A7AY (E kit). More Details >>

    • No:21290
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Even though the maximum frequency setting is changed using CC-Link, the running frequency is not changed. By writing the set frequency to the remote register... More Details >>

    • No:21346
    • Release Date:2018/08/22 16:27
  • Output frequency

    For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>

    • No:21682
    • Release Date:2018/08/22 16:28
  • Stop-on-contact control

    Set Pr.270 (Stop-on-contact control) to "1".Set Pr.184 (RES terminal function selection) to "3" to choose the RT signal function.When the terminals RL and RT... More Details >>

    • No:21691
    • Release Date:2018/08/22 16:28
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29