  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) instead of Pr.1 (Maximum frequency).   More Details >>

    • No:21802
    • Release Date:2018/08/22 16:29
  • Frequency setting

    No.Just turn the setting dial to select a frequency and press the "SET" key, and the inverter operates at the selected frequency. More Details >>

    • No:21798
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21792
    • Release Date:2018/08/22 16:29
  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "100".Displaying the setting frequency while the inverter is stopped and the output frequency while it is op... More Details >>

    • No:21783
    • Release Date:2018/08/22 16:29
  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>

    • No:21765
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency).   More Details >>

    • No:21744
    • Release Date:2018/08/22 16:29
  • Graph function in FR-Configurator

    Even the USB is used, FR Configurator requires at least 50 ms sampling time (for each monitoring item). In this case, since three types of data are monitored... More Details >>

    • No:21310
    • Release Date:2018/08/22 16:26
  • Speed command

    Calibrate the terminal 2 bias. More Details >>

    • No:21281
    • Release Date:2018/08/22 16:26