  • Frequency setting

    From the LED, it is considered that the operation mode Pr.79 is set to "3".The PU and EXT LEDs turn ON with this setting.In this state, you cannot change bet... More Details >>

    • No:21741
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) instead of Pr.1 (Maximum frequency).   More Details >>

    • No:21802
    • Release Date:2018/08/22 16:29
  • FR-PA07

    1. Press the PU/EXT key on the operation panel FR-PA07 to choose the PU operation mode. Set Pr.161 (Frequency setting/key lock operation selection) to "1" an... More Details >>

    • No:21761
    • Release Date:2018/08/22 16:29
  • Parameter

    No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>

    • No:21769
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>

    • No:21789
    • Release Date:2018/08/22 16:29
  • CC-Link

    The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>

    • No:21828
    • Release Date:2018/08/22 16:29
  • Setting dial

    Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>

    • No:21846
    • Release Date:2018/08/22 16:29
  • Terminal FM

    Set Pr.56 (Current monitor reference) to "10A". More Details >>

    • No:21865
    • Release Date:2018/08/22 16:29
  • CC-Link

    You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>

    • No:21892
    • Release Date:2018/08/22 16:29