FAQ within [ FREQROL-E700 ]
-
Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>
- No:21244
- Release Date:2018/08/22 16:26
-
Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>
- No:21330
- Release Date:2018/08/22 16:27
-
The parameter setting software we provide is the FR Configurator (FR-SW3-SETUP-WJ). You must purchase it to use. Once you purchase the software, you can upgr... More Details >>
- No:21673
- Release Date:2018/08/22 16:28
-
Pr.1 (Maximum frequency) or Pr.18 (High speed maximum frequency). More Details >>
- No:21805
- Release Date:2018/08/22 16:29
-
Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>
- No:21833
- Release Date:2018/08/22 16:29
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
-
Connect the wire to the optional FR-A7NC's terminal block. (The terminal block is detachable.) More Details >>
- No:21875
- Release Date:2018/08/22 16:29
-
Check if the CC-Link wires are short-circuited and/or station numbers are duplicated. More Details >>
- No:21891
- Release Date:2018/08/22 16:29
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
You can do so by setting Pr.73 to "10" or "11". (For A700/F700 (P), supply negative input to the terminal 1.) More Details >>