    You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>

    • No:21905
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Use Pr.125 (Terminal 2 frequency setting gain frequency).  More Details >>

    • No:21913
    • Release Date:2018/08/22 16:30
  • Safety stop function of the FR-D700/FR-E700

    It is recommended to install the magnetic contactor on the input side of the inverter for safety. The category 3 can be satisfied without installing it. More Details >>

    • No:20837
    • Release Date:2018/08/22 16:24
  • Operation panel (DU04)

    The FR-DU04 can be used in the 700 series inverters, however, some restrictions apply and parameter copy is disabled. More Details >>

    • No:21261
    • Release Date:2018/08/22 16:26
  • Offline auto tuning

    When auto tuning completes normally, the setting value of Pr.96 (Auto tuning setting/status) is changed to "3". When it is not changed, check the set paramet... More Details >>

    • No:21353
    • Release Date:2018/08/22 16:27
  • Frequency meter and calibration resistor

    Frequency meter: YM206NRI 1 mA Calibration resistor: RV24YN 10 k?. More Details >>

    • No:21357
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Set Pr.79 (Operation mode) to "3".When a signal is input to the terminal RL, the inverter starts operating at the frequency set with Pr.6 (Multi-speed settin... More Details >>

    • No:21791
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Base frequency setting value

    Set the rated frequency of the motor used to it.  More Details >>

    • No:21814
    • Release Date:2018/08/22 16:29