Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29
-
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
- No:21845
- Release Date:2018/08/22 16:29
-
1. You can reset the inverter from an external terminal.You can do it without regard to the setting of Pr.338 (Communication operation command source) and Pr... More Details >>
- No:21837
- Release Date:2018/08/22 16:29
-
This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>
- No:21743
- Release Date:2018/08/22 16:29
-
Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>
- No:21739
- Release Date:2018/08/22 16:29
-
Set Pr.125 (Terminal 2 frequency setting gain frequency) to "50 Hz".Set Pr.1 (Maximum frequency) to "50 Hz". More Details >>
- No:21720
- Release Date:2018/08/22 16:29
-
Change Pr.126 (Terminal 4 frequency setting gain frequency). More Details >>
- No:21677
- Release Date:2018/08/22 16:28
-
Since the multi-speed is given a higher priority, the setting by the setting dial is not enabled unless all of the multi-speed signals are OFF. More Details >>
- No:21302
- Release Date:2018/08/22 16:26
-
NET mode, external operation switching
You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>
- No:21906
- Release Date:2018/08/22 16:30
-
When the pulse is counted and displayed, 1440 pulses are output with the frequency of the inverter is 60 Hz. Since these pulses are limited to 2400 pulses, a... More Details >>
- No:21334
- Release Date:2018/08/22 16:27