  • Operation mode setting value

    Set Pr.79 to "2" (external operation mode).    More Details >>

    • No:21818
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21792
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>

    • No:21784
    • Release Date:2018/08/22 16:29
  • Program command

    This subroutine is to check the data link status and needs to be executed only once at the start of the program. More Details >>

    • No:21767
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>

    • No:21725
    • Release Date:2018/08/22 16:29
  • Switching between external operation and NET operation

    You can write frequency setting by setting Pr.339 (Communication speed command source) to "0". More Details >>

    • No:21687
    • Release Date:2018/08/22 16:28
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28