To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>
- No:21799
- Release Date:2018/08/22 16:29
-
Since the Advanced magnetic flux vector control method uses slip compensation to compensate the frequency, the value is not shown as exactly 60 Hz.For V/F co... More Details >>
- No:21807
- Release Date:2018/08/22 16:29
-
First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>
- No:21808
- Release Date:2018/08/22 16:29
-
External multi-speed setting and multi-speed command
It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>
- No:21815
- Release Date:2018/08/22 16:29
-
You can check the fault records with Pr.544 (CC-Link extended setting) set to "12" for double setting.Set H74 for the instruction code and turn ON RYF. More Details >>
- No:21829
- Release Date:2018/08/22 16:29
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
-
You also need to set Pr.79 (Operation mode) to "3". More Details >>
- No:21844
- Release Date:2018/08/22 16:29
-
The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>
- No:21849
- Release Date:2018/08/22 16:29
-
The operation panels of the FR-E700, FR-D700, and FR-F700PJ are not detachable.Therefore, it cannot be attached to the enclosure surface.You can use the opti... More Details >>
- No:21851
- Release Date:2018/08/22 16:29
-
To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>
- No:21852
- Release Date:2018/08/22 16:29