  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26
  • Model selection

    Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>

    • No:21244
    • Release Date:2018/08/22 16:26
  • Output signal

    The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>

    • No:20995
    • Release Date:2018/08/22 16:25
  • Magnetic flux vector control

    For low-speed operation, perform auto tuning and use (Advanced) magnetic flux vector control. More Details >>

    • No:21810
    • Release Date:2018/08/22 16:29
  • Frequency setting

    No.Just turn the setting dial to select a frequency and press the "SET" key, and the inverter operates at the selected frequency. More Details >>

    • No:21798
    • Release Date:2018/08/22 16:29
  • Frequency setting

    It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>

    • No:21733
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Replacement

    The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>

    • No:21248
    • Release Date:2018/08/22 16:26
  • Control terminal

    Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>

    • No:21845
    • Release Date:2018/08/22 16:29
  • Auto tuning

    If "1" is not shown on the frequency monitor, some of the parameters necessary for auto tuning may not be set correctly.Set rated motor current of Pr.81 (Num... More Details >>

    • No:21751
    • Release Date:2018/08/22 16:29