  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Frequency setting

    As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match.   More Details >>

    • No:21795
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You cannot calibrate the frequency around the middle of the current input range.The inverter determines the top and bottom points in the bias/gain adjustment... More Details >>

    • No:21736
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • PU operation

    The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>

    • No:21694
    • Release Date:2018/08/22 16:28
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • Parameter setting software

    The parameter setting software we provide is the FR Configurator (FR-SW3-SETUP-WJ). You must purchase it to use. Once you purchase the software, you can upgr... More Details >>

    • No:21673
    • Release Date:2018/08/22 16:28
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • External 0 to 10 VDC input

    Checking terminals used:Are the terminals MRS and RES open?Are the terminals STR and SD short-circuited correctly?Is the voltage/current switch of the termin... More Details >>

    • No:21916
    • Release Date:2018/08/22 16:30
  • Frequency setting

    The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>

    • No:21806
    • Release Date:2018/08/22 16:29