Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>
- No:21675
- Release Date:2018/08/22 16:28
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
-
No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>
- No:21911
- Release Date:2018/08/22 16:30
-
For the inverter, the option card FR-A7NC is necessary. More Details >>
- No:21897
- Release Date:2018/08/22 16:29
-
Check the connection with the meter.If the terminal FM is connected to the positive terminal and the terminal SD is connected to the negative terminal of the... More Details >>
- No:21762
- Release Date:2018/08/22 16:29
-
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>
- No:21707
- Release Date:2018/08/22 16:29
-
Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>
- No:21286
- Release Date:2018/08/22 16:26
-
Create a ladder program to read inverter faults on the programmable controller.Set the instruction code (H74-H77) and turn ON the instruction code execution ... More Details >>
- No:21886
- Release Date:2018/08/22 16:29
-
When turning the setting dial to set the frequency, press the "SET" key while the desired value blinks. (The setting frequency and "F" flicker alternately.) More Details >>
- No:21742
- Release Date:2018/08/22 16:29