When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
-
Calibrate the terminal 2 bias. More Details >>
- No:21281
- Release Date:2018/08/22 16:26
-
Not available for the FR-E700-SC. For the 485 communication with the terminal block, use the standard FR-E700. More Details >>
- No:21130
- Release Date:2018/08/22 16:26
-
Safety stop function of the FR-D700/FR-E700
It is recommended to install the magnetic contactor on the input side of the inverter for safety. The category 3 can be satisfied without installing it. More Details >>
- No:20837
- Release Date:2018/08/22 16:24
-
Use Pr.125 (Terminal 2 frequency setting gain frequency). More Details >>
- No:21913
- Release Date:2018/08/22 16:30
-
You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>
- No:21905
- Release Date:2018/08/22 16:30
-
Yes. The FR-A7NC E kit contains a dedicated front cover since its size changes by the installed board.You can additionally purchase the FR-A7NC E kit cover o... More Details >>
- No:21889
- Release Date:2018/08/22 16:29
-
Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29
-
Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode). More Details >>
- No:21863
- Release Date:2018/08/22 16:29
-
Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>
- No:21846
- Release Date:2018/08/22 16:29