The operation command source is automatically transferred to the connected FR-PU07 or FR-PA07. More Details >>
- No:21700
- Release Date:2018/08/22 16:28
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
-
Connect the brake resistor to the terminal P and terminal PR. (For the FR-A700-7.5K or lower, remove the jumper of the terminals PR and PX.) Do not remove th... More Details >>
- No:21333
- Release Date:2018/08/22 16:27
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
Calibrate the terminal 2 bias. More Details >>
- No:21281
- Release Date:2018/08/22 16:26
-
You can select deceleration stop by setting Pr.502 (Stop mode selection at communication error). (Select from coasting to stop, deceleration to stop, and con... More Details >>
- No:21892
- Release Date:2018/08/22 16:29
-
Use Pr.542 (Station number). More Details >>
- No:21876
- Release Date:2018/08/22 16:29
-
When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>
- No:21842
- Release Date:2018/08/22 16:29
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
-
Turn ON the monitor command RYC. More Details >>
- No:21826
- Release Date:2018/08/22 16:29