FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E700
FAQ
Keyword Search
FAQ within [ FREQROL-E700 ]
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
-
Use Pr.542 to set the station number and Pr.543 to set the baud rate.To set the baud rate to 10 Mbps, set Pr.543 to "4". More Details >>
- No:21839
- Release Date:2018/08/22 16:29
-
10 VDC voltage from terminal 10
Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>
- No:21727
- Release Date:2018/08/22 16:29
-
When auto tuning completes normally, the setting value of Pr.96 (Auto tuning setting/status) is changed to "3". When it is not changed, check the set paramet... More Details >>
- No:21353
- Release Date:2018/08/22 16:27
-
Number of stations that can be set in FR Configurator
The station numbers that can be set differ depending on the version of FR-Configurator (FR-SW3-SETUP-WJ) setup software. For Ver.2.00 or later, station numbe... More Details >>
- No:21305
- Release Date:2018/08/22 16:26
-
First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>
- No:21808
- Release Date:2018/08/22 16:29
-
As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match. More Details >>
- No:21795
- Release Date:2018/08/22 16:29
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
Auto tuning can help to apply appropriate voltage to the load and decrease the current. Since the electronic thermal O/L relay trips, check that the rated mo... More Details >>
- No:21292
- Release Date:2018/08/22 16:26
-
Multi-speed setting and external potentiometer
The multi-speed setting is prioritized.The external potentiometer setting is effective when the multi-speed signal is not input. More Details >>
- No:21773
- Release Date:2018/08/22 16:29
231-240 of Total 393