  • Output frequency

    When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>

    • No:21259
    • Release Date:2018/08/22 16:26
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) or Pr.18 (High speed maximum frequency).   More Details >>

    • No:21805
    • Release Date:2018/08/22 16:29
  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Operation panel

    If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>

    • No:21343
    • Release Date:2018/08/22 16:27
  • Amount of heat generated

    Refer to the FR-A700/F700/E700/D700 series TECHNICAL MANUAL (section 3.7.2) and the Technical News. The FR-A700/F700/E700/D700 series TECHNICAL MANUAL can be... More Details >>

    • No:21263
    • Release Date:2018/08/22 16:26
  • Life diagnosis

    When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>

    • No:21283
    • Release Date:2018/08/22 16:26
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>

    • No:21797
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>

    • No:21843
    • Release Date:2018/08/22 16:29