FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E700
FAQ
Keyword Search
FAQ within [ FREQROL-E700 ]
-
You can use the setting dial to set the frequency during operation even if Pr.77 is not set to "2".Setting Pr.77 to "2" allows for changing the parameter set... More Details >>
- No:21786
- Release Date:2018/08/22 16:29
-
Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>
- No:21772
- Release Date:2018/08/22 16:29
-
To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>
- No:21771
- Release Date:2018/08/22 16:29
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29
-
No. the torque cannot be limited by using Pr.9.Set Pr.277 (Stall prevention current switching) to "1".The value of Pr.22 (Stall prevention operation level) w... More Details >>
- No:21766
- Release Date:2018/08/22 16:29
-
Set it to "13" (Constant-torque). More Details >>
- No:21752
- Release Date:2018/08/22 16:29
-
You cannot calibrate the frequency around the middle of the current input range.The inverter determines the top and bottom points in the bias/gain adjustment... More Details >>
- No:21736
- Release Date:2018/08/22 16:29
-
FR-A7AR E kit (Relay output function)
Yes, you can set all of the three relay contacts to fault contacts.Set Pr.320 (RA1 output selection), 321 (RA2 output selection), and 322 (RA3 output selecti... More Details >>
- No:21712
- Release Date:2018/08/22 16:29
-
There is a priority between the setting dial and multi-speed settings.Since the multi-speed setting is given a higher priority, the setting by the setting di... More Details >>
- No:21702
- Release Date:2018/08/22 16:29
-
The FR-E700 series is not equipped with the EMC filter. More Details >>
- No:21667
- Release Date:2018/08/22 16:28
241-250 of Total 393