FAQ
Keyword Search
FAQ within [ FREQROL-E700 ]
-
You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>
- No:21787
- Release Date:2018/08/22 16:29
-
Set Pr.79 to "2" (external operation mode). More Details >>
- No:21818
- Release Date:2018/08/22 16:29
-
Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>
- No:21797
- Release Date:2018/08/22 16:29
-
The first priority window of the monitor may be set to the current.When the current is displayed on the monitor (the unit is "A"), press "SET" to switch to t... More Details >>
- No:21765
- Release Date:2018/08/22 16:29
-
Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>
- No:21879
- Release Date:2018/08/22 16:29
-
Operation mode, PU operation mode switching
Change Pr.340 (Communication startup mode selection) from "1" to "0".Power OFF and then ON the inverter.Operate the inverter according to the value of Pr.79 ... More Details >>
- No:21870
- Release Date:2018/08/22 16:29
-
You cannot use the setting dial while the terminals JOG and SD are turned ON.When performing JOG operation using external signals, set Pr.79 (Operation mode)... More Details >>
- No:21823
- Release Date:2018/08/22 16:29
-
The FR Configurator FR-SW3-SETUP-WJ can only allow for test operation.Since this is a tool to support the system launch and maintenance, it is not designed f... More Details >>
- No:21914
- Release Date:2018/08/22 16:30
-
No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>
- No:21776
- Release Date:2018/08/22 16:29
-
From the LED, it is considered that the operation mode Pr.79 is set to "3".The PU and EXT LEDs turn ON with this setting.In this state, you cannot change bet... More Details >>
- No:21741
- Release Date:2018/08/22 16:29