FAQ within [ FREQROL-E700 ]
-
You can start/stop operation, set the frequency, read/write parameters, and monitor the inverter via CC-Link communication. More Details >>
- No:21901
- Release Date:2018/08/22 16:29
-
The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>
- No:20994
- Release Date:2018/08/22 16:25
-
Since the operation panel and PU connector cannot be specified for command source at the same time, they cannot be used together. More Details >>
- No:21349
- Release Date:2018/08/22 16:27
-
Both 200 V class and 400 V class are suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 264 V maximum (528 V f... More Details >>
- No:21358
- Release Date:2018/08/22 16:27
-
FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>
- No:21707
- Release Date:2018/08/22 16:29
-
The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>
- No:20995
- Release Date:2018/08/22 16:25
-
The output voltage will not be imbalanced when the inverter is used. (Since AC is converted into DC and then into AC, the output voltage is hardly effected f... More Details >>
- No:21278
- Release Date:2018/08/22 16:26
-
You can use optional items, such as enclosure surface operation panel FR-PA07 and parameter unit FR-PU07.Use the PU connector of the inverter for connection.... More Details >>
- No:21832
- Release Date:2018/08/22 16:29
-
The FR Configurator FR-SW3-SETUP-WJ can only allow for test operation.Since this is a tool to support the system launch and maintenance, it is not designed f... More Details >>
- No:21914
- Release Date:2018/08/22 16:30
-
Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>
- No:21679
- Release Date:2018/08/22 16:28