  • 4 to 20 mA output

    Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>

    • No:21246
    • Release Date:2018/08/22 16:26
  • Rated motor current setting

    No. the torque cannot be limited by using Pr.9.Set Pr.277 (Stall prevention current switching) to "1".The value of Pr.22 (Stall prevention operation level) w... More Details >>

    • No:21766
    • Release Date:2018/08/22 16:29
  • Auto tuning

    When offline auto tuning ends normally, the setting of this parameter changes to "3".This means that auto tuning completed normally.If the setting value is "... More Details >>

    • No:21748
    • Release Date:2018/08/22 16:29
  • Noise filter

    The noise filter is not built-in the FR-E700 series. It is built in the FR-A700/F700 series with the 55K or lower capacity. More Details >>

    • No:21276
    • Release Date:2018/08/22 16:26
  • Brake unit

    The brake unit operates when the bus voltage exceeds the brake operation voltage. More Details >>

    • No:21272
    • Release Date:2018/08/22 16:26
  • Changing the control method

    Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>

    • No:21245
    • Release Date:2018/08/22 16:26
  • CC-Link

    You can select from the output power (in 0.01 kW units) and cumulative energy (in 1 kWh/0.01 kWh units). More Details >>

    • No:21885
    • Release Date:2018/08/22 16:29
  • Operation panel LED

    No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>

    • No:21776
    • Release Date:2018/08/22 16:29
  • Operation panel (FR-PA02)

    Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>

    • No:21730
    • Release Date:2018/08/22 16:29
  • Auto tuning

    With the monitor indicator "1", there is no problem with the parameter setting of auto tuning. Check if the terminals MRS and SD are not shortened in the wir... More Details >>

    • No:21294
    • Release Date:2018/08/22 16:26