Supported model for FR-Configurator
The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>
- No:21314
- Release Date:2018/08/22 16:26
-
It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>
- No:21785
- Release Date:2018/08/22 16:29
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>
- No:21728
- Release Date:2018/08/22 16:29
-
It is the fixing screw for the inverter cooling fan cover.The size and number of screws depend on the model and capacity.(When exporting the product to the E... More Details >>
- No:21746
- Release Date:2018/08/22 16:29
-
Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
-
Electronic thermal O/L relay setting
When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>
- No:21676
- Release Date:2018/08/22 16:28
-
Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>
- No:21267
- Release Date:2018/08/22 16:26
-
There is no problem with the wiring. Keep the rating (24 VDC, 0.1 A) of the terminal PC. More Details >>
- No:21342
- Release Date:2018/08/22 16:27
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29