  • Full scale frequency

    You can change the full-scale value by changing Pr.55 (Frequency monitor reference). The initial setting is 60 Hz. More Details >>

    • No:21672
    • Release Date:2018/08/22 16:28
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29
  • NET operation mode

    Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>

    • No:21319
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • Switching between external operation and NET operation

    You can monitor the fault output in both NET operation and external operation. More Details >>

    • No:21686
    • Release Date:2018/08/22 16:28
  • Multi-speed setting

    Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>

    • No:21772
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Up to 30 m. (To avoid noise and voltage drop)   More Details >>

    • No:21910
    • Release Date:2018/08/22 16:30
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Frequency command

    Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>