FAQ within [ FREQROL-E700 ]

41-50 of Total 393

prev 5 / 40page next
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • Frequency setting

    When using the setting dial to set the frequency, turn the dial and display the frequency. Then, press the "SET" key while the desired value flickers.The fre... More Details >>

    • No:21848
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Start command

    Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>

    • No:21285
    • Release Date:2018/08/22 16:26
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • JOG function

    When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>

    • No:21760
    • Release Date:2018/08/22 16:29
  • Switching between PU and NET operations

    Even after setting Pr.340 to "10", the change is reflected after resetting the power supply.Perform the power reset.Since changes to the communication parame... More Details >>

    • No:21696
    • Release Date:2018/08/22 16:28
  • MRS setting

    1. For MRS, coasting starts when the MRS contact turns ON. For Pr.250 = "0",IM is coasting immediately when the start signal is turned OFF.  2. No. Set eithe... More Details >>

    • No:21360
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>

    • No:21803
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>

    • No:21787
    • Release Date:2018/08/22 16:29