  • PU operation

    Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21863
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Maximum frequency

    If you try to change a parameter in other than the PU operation mode, the mode specification error "Er4" may occur.Set the parameters in the PU operation mod... More Details >>

    • No:21778
    • Release Date:2018/08/22 16:29
  • Adjustment of analog gain

    Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>

    • No:21689
    • Release Date:2018/08/22 16:28
  • Proportional band of multiple inverters

    By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>

    • No:21250
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Up to 30 m. (To avoid noise and voltage drop)   More Details >>

    • No:21910
    • Release Date:2018/08/22 16:30
  • Using external potentiometer and multi-speed operation together

    You can use an external potentiometer and multi-speed operation together.When an external potentiometer signal input and multi-speed setting occur simultaneo... More Details >>

    • No:21920
    • Release Date:2018/08/22 16:30
  • CC-Link

    Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>

    • No:21833
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Operation panel LED

    No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>

    • No:21776
    • Release Date:2018/08/22 16:29