FAQ within [ FREQROL-E700 ]

71-80 of Total 393

prev 8 / 40page next
  • FR-PA07

    Basically it is not possible due to the operation command source.However, if Pr.77 (Parameter write selection) is set to "2", you can use both the FR-PA07 an... More Details >>

    • No:21698
    • Release Date:2018/08/22 16:28
  • Tuning

    Check the parameters listed below necessary for tuning again.Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, Pr.84, and Pr.96 More Details >>

    • No:21726
    • Release Date:2018/08/22 16:29
  • Advanced magnetic flux vector control

    Check the parameters necessary for tuning again.Check if Pr.9 (Electronic thermal O/L relay) and Pr.81 (Number of motor poles) are set correctly. More Details >>

    • No:21754
    • Release Date:2018/08/22 16:29
  • Stop-on-contact control of the FR-E700

    The stop-on-contact control becomes invalid when the start command is turned OFF during the stop-on-contact control and the machine is decelerated to a stop ... More Details >>

    • No:20822
    • Release Date:2018/08/22 16:24
  • Operation panel for FR-E500

    The operation panel FR-PA02 for the FR-E500 can be used for these models.You need the FR-E5P (back cover adapter set) and FR-C20□ (connection cable) for the ... More Details >>

    • No:21860
    • Release Date:2018/08/22 16:29
  • Parameter setting

    You can perform forward and reverse operations with the RUN key on the operation panel by setting Pr.40 (RUN key rotation direction selection). More Details >>

    • No:21719
    • Release Date:2018/08/22 16:29
  • Auto tuning

    If you have already set other parameters necessary for tuning (Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, and Pr.84), press the MODE button to return to the frequency... More Details >>

    • No:21750
    • Release Date:2018/08/22 16:29
  • CC-Link

    You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>

    • No:21827
    • Release Date:2018/08/22 16:29
  • Electronic thermal O/L relay

    Check that the correct rated motor current is set in Pr.9 (Electronic thermal O/L relay). No parameter is available for setting the operation time of the ele... More Details >>

    • No:21291
    • Release Date:2018/08/22 16:26
  • Operation mode setting

    The stop-on-contact control does not function in the combined operation mode.  Perform the control in the External operation mode. More Details >>

    • No:21354
    • Release Date:2018/08/22 16:27