  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • CC-Link

    Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>

    • No:21903
    • Release Date:2018/08/22 16:30
  • Offline auto tuning

    Leave the setting of Pr.96 as "3". It indicates that auto tuning has been completed and the motor constant has been read. When it is changed unnecessarily, t... More Details >>

    • No:21352
    • Release Date:2018/08/22 16:27
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • NET mode, external operation switching

    You can switch between the NET mode and external operation.Assign the X66 signal (Operation switching) to an unused terminal for switching.Also, set Pr.79 (O... More Details >>

    • No:21906
    • Release Date:2018/08/22 16:30
  • Terminal FM meter connection

    Check the connection with the meter.If the terminal FM is connected to the positive terminal and the terminal SD is connected to the negative terminal of the... More Details >>

    • No:21762
    • Release Date:2018/08/22 16:29
  • Auto tuning

    If "1" is not shown on the frequency monitor, some of the parameters necessary for auto tuning may not be set correctly.Set rated motor current of Pr.81 (Num... More Details >>

    • No:21751
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Yes, you can set Pr.20 to 20 Hz. More Details >>

    • No:21683
    • Release Date:2018/08/22 16:28