FAQ within [ FREQROL-E700 ]

1-10 of Total 394

prev 1 / 40page next
  • Safety stop function of the FR-D700/FR-E700

    It is recommended to install the magnetic contactor on the input side of the inverter for safety. The category 3 can be satisfied without installing it. More Details >>

    • No:20837
    • Release Date:2018/08/22 16:24
  • Operation panel LED

    No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>

    • No:21776
    • Release Date:2018/08/22 16:29
  • FR-E700KNC

    The inverter is reset. More Details >>

    • No:20869
    • Release Date:2018/08/22 16:24
  • Parameter setting

    You can perform forward and reverse operations with the RUN key on the operation panel by setting Pr.40 (RUN key rotation direction selection). More Details >>

    • No:21719
    • Release Date:2018/08/22 16:29
  • FR-PA07

    1. Press the PU/EXT key on the operation panel FR-PA07 to choose the PU operation mode. Set Pr.161 (Frequency setting/key lock operation selection) to "1" an... More Details >>

    • No:21761
    • Release Date:2018/08/22 16:29
  • Single-phase 200 V input

    The FR-E720S series and D720S series conform to the single-phase 200 V input specifications. More Details >>

    • No:21723
    • Release Date:2018/08/22 16:29
  • Advanced magnetic flux vector control

    Check the parameters necessary for tuning again.Check if Pr.9 (Electronic thermal O/L relay) and Pr.81 (Number of motor poles) are set correctly. More Details >>

    • No:21754
    • Release Date:2018/08/22 16:29
  • Advanced magnetic flux vector control

    To use Advanced magnetic flux vector control, basically set Pr.9, Pr.80, Pr.81, Pr.71, and Pr.800.Auto tuning is necessary in some cases. Set Pr.83, Pr.84, a... More Details >>

    • No:21755
    • Release Date:2018/08/22 16:29
  • Specifications

    It can be driven by connecting single-phase 200 V to the terminals R and S. In this case, the load current must be one-third or less of the inverter rated cu... More Details >>

    • No:21282
    • Release Date:2018/08/22 16:26
  • FR-PA07

    No. The "RUN" key on the FR-PA07 does not work.The start command is accepted from the external source. More Details >>

    • No:21703
    • Release Date:2018/08/22 16:29

1-10 of Total 394