  • Amount of heat generated

    Refer to the FR-A700/F700/E700/D700 series TECHNICAL MANUAL (section 3.7.2) and the Technical News. The FR-A700/F700/E700/D700 series TECHNICAL MANUAL can be... More Details >>

    • No:21263
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>

    • No:21907
    • Release Date:2018/08/22 16:30
  • Monitor indicator

    Press the "SET" key once while the output frequency is monitored.The unit indicator LED changes from "Hz" to "A" and the monitor display changes to the current. More Details >>

    • No:21764
    • Release Date:2018/08/22 16:29
  • Rated frequency setting

    Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>

    • No:21280
    • Release Date:2018/08/22 16:26
  • Operation panel (DU04)

    The FR-DU04 can be used in the 700 series inverters, however, some restrictions apply and parameter copy is disabled. More Details >>

    • No:21261
    • Release Date:2018/08/22 16:26
  • Terminal FM

    Set Pr.56 (Current monitor reference) to "10A". More Details >>

    • No:21865
    • Release Date:2018/08/22 16:29
  • Frequency setting

    From the LED, it is considered that the operation mode Pr.79 is set to "3".The PU and EXT LEDs turn ON with this setting.In this state, you cannot change bet... More Details >>

    • No:21741
    • Release Date:2018/08/22 16:29
  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Base frequency setting value

    Set the rated frequency of the motor used to it.  More Details >>

    • No:21814
    • Release Date:2018/08/22 16:29
  • JOG function

    When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>

    • No:21760
    • Release Date:2018/08/22 16:29