Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-D700 ]

111-120 of Total 261

prev 12 / 27page next
  • Frequency setting

    Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>

    • No:21789
    • Release Date:2018/08/22 16:29
  • Frequency setting

    No.Just turn the setting dial to select a frequency and press the "SET" key, and the inverter operates at the selected frequency. More Details >>

    • No:21798
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>

    • No:21803
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Pr.1 (Maximum frequency) or Pr.18 (High speed maximum frequency).   More Details >>

    • No:21805
    • Release Date:2018/08/22 16:29
  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • Operation mode setting value

    Set Pr.79 to "2" (external operation mode).    More Details >>

    • No:21818
    • Release Date:2018/08/22 16:29
  • Running frequency

    The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>

    • No:21820
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>

    • No:21842
    • Release Date:2018/08/22 16:29
  • Control terminal

    Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>

    • No:21845
    • Release Date:2018/08/22 16:29

111-120 of Total 261

Inquiries