FAQ within [ FREQROL-D700 ]

111-120 of Total 261

prev 12 / 27page next
  • Control terminal

    Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>

    • No:21845
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Multi-speed setting

    Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>

    • No:21772
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Terminal

    Change Pr.126 (Terminal 4 frequency setting gain frequency). More Details >>

    • No:21677
    • Release Date:2018/08/22 16:28
  • Graph function in FR-Configurator

    Even the USB is used, FR Configurator requires at least 50 ms sampling time (for each monitoring item). In this case, since three types of data are monitored... More Details >>

    • No:21310
    • Release Date:2018/08/22 16:26
  • Running frequency

    The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>

    • No:21820
    • Release Date:2018/08/22 16:29
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • Operation mode setting

    Rapid blinking of the RUN LED indicates that the frequency setting command has not been input or the output stop signal has been input.Since Pr.79 is set to ... More Details >>

    • No:21853
    • Release Date:2018/08/22 16:29
  • Connecting ammeter to output side

    Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>

    • No:21681
    • Release Date:2018/08/22 16:28