FAQ within [ FREQROL-D700 ]
-
Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it. More Details >>
- No:21711
- Release Date:2018/08/22 16:29
-
The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>
- No:21694
- Release Date:2018/08/22 16:28
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
Even while the inverter is operating, you can use the setting dial to change the frequency and then press the SET key and the inverter operates at the new fr... More Details >>
- No:21739
- Release Date:2018/08/22 16:29
-
The full scale of the frequency is initially set to 60 Hz and the frequency indication becomes the full scale at 60 Hz operation.To change the indication val... More Details >>
- No:21866
- Release Date:2018/08/22 16:29
-
Frequency manual controller FR-AX
Considering voltage drop of the internal power supply and influence by noise, the wiring length should be 30 m or less. More Details >>
- No:21809
- Release Date:2018/08/22 16:29
-
You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>
- No:21680
- Release Date:2018/08/22 16:28
-
Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>
- No:21674
- Release Date:2018/08/22 16:28
-
Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>
- No:21249
- Release Date:2018/08/22 16:26
-
Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode). More Details >>