FAQ within [ FREQROL-D700 ]

151-160 of Total 260

prev 16 / 26page next
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Instruction manual

    For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>

    • No:21341
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Frequency setting

    No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>

    • No:21911
    • Release Date:2018/08/22 16:30
  • Radio Act

    The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>

    • No:20994
    • Release Date:2018/08/22 16:25
  • Output frequency

    When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>

    • No:21259
    • Release Date:2018/08/22 16:26
  • Motor coasting

    To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>

    • No:21271
    • Release Date:2018/08/22 16:26
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Brake resistor

    Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>

    • No:21330
    • Release Date:2018/08/22 16:27