As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match. More Details >>
- No:21795
- Release Date:2018/08/22 16:29
-
Check that the correct rated motor current is set in Pr.9 (Electronic thermal O/L relay). No parameter is available for setting the operation time of the ele... More Details >>
- No:21291
- Release Date:2018/08/22 16:26
-
No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
- No:21365
- Release Date:2018/08/22 16:27
-
Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>
- No:21366
- Release Date:2018/08/22 16:27
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21730
- Release Date:2018/08/22 16:29
-
When auto tuning completes normally, the setting value of Pr.96 (Auto tuning setting/status) is changed to "3". When it is not changed, check the set paramet... More Details >>
- No:21353
- Release Date:2018/08/22 16:27
-
The adapter is not necessary. Only the dedicated cable FR-CB20□ is required. More Details >>
- No:21362
- Release Date:2018/08/22 16:27
-
1. Yes. 2. The standard set by Pr.56. More Details >>
- No:21669
- Release Date:2018/08/22 16:28
-
Connecting it causes no problem. More Details >>
- No:21671
- Release Date:2018/08/22 16:28
-
No. The "RUN" key on the FR-PA07 does not work.The start command is accepted from the external source. More Details >>
- No:21703
- Release Date:2018/08/22 16:29