FAQ within [ FREQROL-D700 ]
-
1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>
- No:21359
- Release Date:2018/08/22 16:27
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
-
Yes, you can set Pr.20 to 20 Hz. More Details >>
- No:21683
- Release Date:2018/08/22 16:28
-
Switching between external operation and NET operation
You can monitor the fault output in both NET operation and external operation. More Details >>
- No:21686
- Release Date:2018/08/22 16:28
-
The operation command source is automatically transferred to the connected FR-PU07 or FR-PA07. More Details >>
- No:21700
- Release Date:2018/08/22 16:28
-
Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>
- No:21728
- Release Date:2018/08/22 16:29
-
No. You cannot change the setting during operation.However, setting Pr.77 (Parameter write selection) to "2" allows for the setting change during operation. ... More Details >>
- No:21734
- Release Date:2018/08/22 16:29
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>
- No:21800
- Release Date:2018/08/22 16:29
-
The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>
- No:21806
- Release Date:2018/08/22 16:29